According to the requirements of "Design Specifications for Electronic Information System Computer Room GB50174-2008", the special cold water storage tank for the cold storage center should be selected and backed up according to the grade of the electronic information system computer room, the building conditions of the computer room, and the calorific value of the equipment. As the emergency backup cold source equipment for the air conditioning system of the entire data center, the cold water storage tank has corresponding requirements in terms of safety, stability, and load matching. Vertical and horizontal, pressure-bearing is divided into 1.0MPA and 1.6MPA, and the corresponding specifications are selected according to the different volumes. The corresponding selection of data center cold storage tanks with a diameter of less than or equal to 4 meters is shown in the table below. Data center cold storage tanks with a diameter of more than 4 meters will need to be fabricated and installed on site according to the design drawings.
Cold storage volume(m³) | Specifications (V/H) | Tank pressure | Tank diameter(mm) | Barrel length(mm) | Head depth | Cylinder wall thickness(mm) | Head wall thickness(mm) | Total length(mm) |
120 | TW-1.0-120-(V/H) | 1.0MP | 3500 | 11200 | 915 | 12 | 12 | 13454 |
3600 | 10600 | 940 | 12 | 12 | 12904 | |||
3800 | 9300 | 990 | 12 | 14 | 11708 | |||
4000 | 8200 | 1040 | 12 | 14 | 10708 | |||
TW-1.6-120-(V/H) | 1.6MP | 3500 | 11200 | 915 | 18 | 18 | 13466 | |
3600 | 10600 | 940 | 18 | 18 | 12916 | |||
3800 | 9300 | 990 | 18 | 20 | 11720 | |||
4000 | 8200 | 1040 | 20 | 20 | 10720 | |||
110 | TW-1.0-110-(V/H) | 1.0MP | 3500 | 10200 | 916 | 12 | 12 | 12454 |
3600 | 9600 | 940 | 12 | 12 | 11904 | |||
3800 | 8400 | 990 | 12 | 14 | 10808 | |||
4000 | 7400 | 1040 | 12 | 14 | 9908 | |||
TW-1.6-110-(V/H) | 1.6MP | 3500 | 10200 | 916 | 18 | 18 | 12466 | |
3600 | 9600 | 940 | 18 | 18 | 11916 | |||
3800 | 8400 | 990 | 18 | 20 | 10820 | |||
4000 | 7400 | 1040 | 20 | 20 | 9920 | |||
100 | TW-1.0-100-(V/H) | 1.0MP | 3500 | 9200 | 915 | 12 | 12 | 11454 |
3600 | 8600 | 940 | 12 | 12 | 10904 | |||
3800 | 7500 | 990 | 12 | 14 | 9808 | |||
4000 | 6600 | 1040 | 12 | 14 | 8908 | |||
TW-1.6-100-(V/H) | 1.6MP | 3500 | 9200 | 915 | 18 | 18 | 11466 | |
3600 | 8600 | 940 | 18 | 18 | 10916 | |||
3800 | 7500 | 990 | 18 | 20 | 9920 | |||
4000 | 6600 | 1040 | 20 | 20 | 9120 | |||
90 | TW-1.0-90-(V/H) | 1.0MP | 3500 | 8200 | 915 | 12 | 12 | 10454 |
3600 | 7600 | 940 | 12 | 12 | 9904 | |||
3800 | 6600 | 990 | 12 | 14 | 9908 | |||
4000 | 5800 | 1040 | 12 | 14 | 8308 | |||
TW-1.6-90-(V/H) | 1.6MP | 3500 | 8200 | 915 | 18 | 18 | 10466 | |
3600 | 7600 | 940 | 18 | 18 | 9916 | |||
3800 | 6600 | 990 | 18 | 20 | 9020 | |||
4000 | 5800 | 1040 | 20 | 20 | 8320 | |||
80 | TW-1.0-80-(V/H) | 1.0MP | 3000 | 10300 | 790 | 10 | 12 | 12312 |
3200 | 8800 | 840 | 10 | 12 | 10912 | |||
3400 | 7700 | 890 | 12 | 12 | 9916 | |||
3500 | 7100 | 915 | 12 | 12 | 9366 | |||
3600 | 6600 | 940 | 12 | 16 | 8666 | |||
3800 | 5700 | 990 | 12 | 16 | 7870 | |||
4000 | 5000 | 1040 | 12 | 16 | 7270 | |||
TW-1.6-80-(V/H) | 1.6MP | 3000 | 10300 | 790 | 16 | 16 | 12312 | |
3200 | 8800 | 840 | 16 | 16 | 10912 | |||
3400 | 7700 | 890 | 16 | 18 | 9916 | |||
3500 | 7100 | 915 | 18 | 18 | 9366 | |||
3600 | 6600 | 940 | 18 | 18 | 8666 | |||
3800 | 5700 | 990 | 20 | 20 | 7870 | |||
4000 | 5000 | 1040 | 20 | 20 | 7270 | |||
70 | TW-1.0-70-(V/H) | 1.0MP | 3000 | 8800 | 790 | 10 | 12 | 10804 |
3200 | 7600 | 840 | 10 | 12 | 9704 | |||
3400 | 6600 | 890 | 12 | 12 | 8804 | |||
3500 | 6100 | 915 | 12 | 12 | 8354 | |||
3600 | 5600 | 940 | 12 | 12 | 7654 | |||
3800 | 4900 | 990 | 12 | 14 | 7058 | |||
4000 | 4200 | 1040 | 12 | 14 | 6458 | |||
TW-1.6-70-(V/H) | 1.6MP | 3000 | 8800 | 790 | 16 | 16 | 10812 | |
3200 | 7600 | 840 | 16 | 16 | 9712 | |||
3400 | 6600 | 890 | 16 | 18 | 8816 | |||
3500 | 6100 | 915 | 18 | 18 | 8366 | |||
3600 | 5600 | 940 | 18 | 18 | 7666 | |||
3800 | 4900 | 990 | 18 | 20 | 7070 | |||
4000 | 4200 | 1040 | 20 | 20 | 6470 | |||
60 | TW-1.0-60-(V/H) | 1.0MP | 3000 | 7500 | 790 | 10 | 12 | 9504 |
3200 | 6400 | 840 | 10 | 12 | 8504 | |||
3400 | 5500 | 890 | 12 | 12 | 7704 | |||
3500 | 5000 | 915 | 12 | 12 | 7254 | |||
3600 | 4700 | 940 | 12 | 12 | 6754 | |||
3800 | 4000 | 990 | 12 | 14 | 6158 | |||
4000 | 3400 | 1040 | 12 | 14 | 5658 | |||
TW-1.6-60-(V/H) | 1.6MP | 3000 | 7500 | 790 | 16 | 16 | 9512 | |
3200 | 6400 | 840 | 16 | 16 | 8512 | |||
3400 | 5500 | 890 | 16 | 18 | 7716 | |||
3500 | 5000 | 915 | 18 | 18 | 7266 | |||
3600 | 4700 | 940 | 18 | 18 | 6766 | |||
3800 | 4000 | 990 | 18 | 20 | 6170 | |||
4000 | 3400 | 1040 | 20 | 20 | 5670 | |||
50 | TW-P1.0-50-(V/H) | 1.0MP | 3000 | 6000 | 790 | 10 | 12 | 8004 |
3200 | 5100 | 840 | 10 | 12 | 7204 | |||
3400 | 4400 | 890 | 12 | 12 | 6604 | |||
3500 | 4000 | 915 | 12 | 12 | 6254 | |||
3600 | 3700 | 940 | 12 | 12 | 5754 | |||
3800 | 3100 | 990 | 12 | 14 | 5258 | |||
4000 | 2600 | 1040 | 12 | 14 | 4858 | |||
TW-P1.6-50-(V/H) | 1.6MP | 3000 | 6000 | 790 | 16 | 16 | 8012 | |
3200 | 5100 | 840 | 16 | 16 | 7212 | |||
3400 | 4400 | 890 | 16 | 18 | 6616 | |||
3500 | 4000 | 915 | 18 | 18 | 6266 | |||
3600 | 3700 | 940 | 18 | 18 | 5766 | |||
3800 | 3100 | 990 | 18 | 20 | 5270 | |||
4000 | 2600 | 1040 | 20 | 20 | 4870 | |||
40 | TW-P1.0-40-(V/H) | 1.0MP | 2600 | 6600 | 690 | 10 | 10 | 8400 |
2800 | 5500 | 740 | 10 | 10 | 7400 | |||
3000 | 4600 | 790 | 10 | 12 | 6604 | |||
3200 | 3900 | 840 | 10 | 12 | 6004 | |||
3400 | 3200 | 890 | 12 | 12 | 5404 | |||
3500 | 3000 | 915 | 12 | 12 | 5254 | |||
3600 | 2700 | 940 | 12 | 12 | 5004 | |||
TW-P1.6-40-(V/H) | 1.6MP | 2600 | 6600 | 690 | 14 | 14 | 8408 | |
2800 | 5500 | 740 | 14 | 16 | 7412 | |||
3000 | 4600 | 790 | 16 | 16 | 6612 | |||
3200 | 3900 | 840 | 16 | 16 | 6012 | |||
3400 | 3200 | 890 | 16 | 18 | 5416 | |||
3500 | 3000 | 915 | 18 | 18 | 5266 | |||
3600 | 2700 | 940 | 18 | 18 | 5016 | |||
Remarks: Horizontal Vertical |
Table 1: Selection comparison table of special cold storage tanks for data centers